A single-phase load draws 9 A (rms) from a 230 V (rms) supply at a power factor of 0.75 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A load takes 45 kW of real power and 29 kvar of reactive power (lagging). Find the apparent power S.
A single-phase motor takes 39 kW at a power factor of 0.7 lagging from a 240 V supply. Find the line current I.
A single-phase motor takes 36 kW at a power factor of 0.7 lagging from a 400 V supply. Find the line current I.
A 50 V (rms), 60 Hz source has an internal impedance Zs = 50 + j3 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A 120 V (rms), 1000 Hz source has an internal impedance Zs = 8 + j6 Ω. The load impedance ZL can be chosen freely. The load for maximum power is built from a resistor in series with a capacitor. Find the capacitance C.
Answer key
- 1. Q = 1369 var
- 2. S = 53.54 kVA
- 3. I = 232.1 A
- 4. I = 128.6 A
- 5. Pmax = 12.5 W
- 6. C = 26.53 µF
Full step-by-step solutions: practise this topic on examproblems.com.