A single-phase load draws 12 A (rms) from a 240 V (rms) supply at a power factor of 0.8 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load connected to a 400 V supply takes 9 kW and 4 kvar. Find the current I drawn from the supply.
A load with impedance Z = 9 + j12 Ω is connected to a 240 V (rms) single-phase supply. Find the real power P it absorbs.
A single-phase motor takes 3 kW at a power factor of 0.9 lagging from a 240 V supply. Find the line current I.
A 15 kVA single-phase transformer supplies a load of 4 kW at a power factor of 0.7 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A 150 kVA single-phase transformer supplies a load of 41 kW at a power factor of 0.85 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. P = 2304 W
- 2. I = 24.62 A
- 3. P = 2304 W
- 4. I = 13.89 A
- 5. ΔP = 10.43 kW
- 6. ΔP = 106.8 kW