A single-phase load draws 3 A (rms) from a 230 V (rms) supply at a power factor of 0.95 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A load takes 26.5 kW of real power and 16 kvar of reactive power (lagging). Find the power factor cos φ.
A load with impedance Z = 6 + j8 Ω is connected to a 240 V (rms) single-phase supply. Find the apparent power S.
A single-phase motor takes 17 kW at a power factor of 0.6 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase load takes 20 kW at a power factor of 0.7 lagging from a 400 V, 50 Hz supply. A 47 µF capacitor is connected in parallel with the load. Find the new line current I.
A single-phase load takes 50 kW at a power factor of 0.65 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
Answer key
- 1. Q = 215.5 var
- 2. cos φ = 0.8561
- 3. S = 5760 VA
- 4. Q = 22.67 kvar
- 5. I = 67.34 A
- 6. Inew = 231.5 A
Full step-by-step solutions: practise this topic on examproblems.com.