A single-phase load draws 5 A (rms) from a 120 V (rms) supply at a power factor of 0.65 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 9 A and 1449 W. Find the reactive power Q taken by the load.
An inductive load takes 7 A and 672 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A single-phase motor takes 12 kW at a power factor of 0.65 lagging from a 230 V supply. Find the line current I.
A single-phase load takes 40 kW at a power factor of 0.75 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the new line current Inew.
A single-phase load takes 9 kW at a power factor of 0.75 lagging from a 240 V, 60 Hz supply. A 68 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
Answer key
- 1. Q = 456 var
- 2. Q = 1478 var
- 3. X = 10.29 Ω
- 4. I = 80.27 A
- 5. Inew = 189 A
- 6. cos φ = 0.8124