A load takes 23.5 kW of real power and 28 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A single-phase load draws 9 A (rms) from a 240 V (rms) supply at a power factor of 0.85 lagging. Find the real power P it takes.
A single-phase motor takes 13 kW at a power factor of 0.6 lagging from a 400 V supply. Find the reactive power Q it draws.
An inductive load takes 19.5 A and 1638 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A single-phase load takes 20 kW at a power factor of 0.75 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the reactive power QC the capacitor must supply.
A 230 V (rms), 60 Hz source has an internal impedance Zs = 10 + j5 Ω. The load impedance ZL can be chosen freely. The load for maximum power is built from a resistor in series with a capacitor. Find the capacitance C.
Answer key
- 1. cos φ = 0.6429
- 2. P = 1836 W
- 3. Q = 17.33 kvar
- 4. X = 4.395 Ω
- 5. QC = 13.58 kvar
- 6. C = 530.5 µF
Full step-by-step solutions: practise this topic on examproblems.com.