A load takes 24 kW of real power and 23 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A single-phase load draws 3 A (rms) from a 230 V (rms) supply at a power factor of 0.7 lagging. Find the reactive power Q it takes.
Two loads are connected in parallel to a 400 V single-phase supply: a 14 kW load at a power factor of 0.75 lagging and a 24 kW heater (unity power factor). Find the overall power factor cos φ seen by the supply.
A single-phase motor takes 3 kW at a power factor of 0.9 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase load takes 50 kW at a power factor of 0.8 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the new line current Inew.
A single-phase load takes 10 kW at a power factor of 0.6 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the new line current Inew.
Answer key
- 1. S = 33.24 kVA
- 2. Q = 492.8 var
- 3. cos φ = 0.9511
- 4. Q = 1.453 kvar
- 5. Inew = 212.6 A
- 6. Inew = 27.17 A