A load takes 37.5 kW of real power and 12 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A single-phase load draws 3 A (rms) from a 240 V (rms) supply at a power factor of 0.95 lagging. Find the reactive power Q it takes.
A single-phase motor takes 18 kW at a power factor of 0.8 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase motor takes 39 kW at a power factor of 0.85 lagging from a 240 V supply. Find the reactive power Q it draws.
A 150 kVA single-phase transformer supplies a load of 55 kW at a power factor of 0.8 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A 100 V (rms), 50 Hz source has an internal impedance Zs = 2 + j10 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
Answer key
- 1. cos φ = 0.9524
- 2. Q = 224.8 var
- 3. Q = 13.5 kvar
- 4. Q = 24.17 kvar
- 5. ΔP = 89.22 kW
- 6. Pmax = 1250 W
Full step-by-step solutions: practise this topic on examproblems.com.