A single-phase load draws 19 A (rms) from a 400 V (rms) supply at a power factor of 0.9 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load draws 3 A (rms) from a 230 V (rms) supply at a power factor of 0.65 lagging. Find the real power P it takes.
A single-phase motor takes 10 kW at a power factor of 0.85 lagging from a 400 V supply. Find the line current I.
An inductive load takes 20 A and 2760 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A 100 V (rms), 50 Hz source has an internal impedance Zs = 8 + j20 Ω. The load impedance ZL can be chosen freely. The load for maximum power is built from a resistor in series with a capacitor. Find the capacitance C.
A single-phase load takes 13 kW at a power factor of 0.65 lagging from a 240 V, 50 Hz supply. A 220 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
Answer key
- 1. P = 6840 W
- 2. P = 448.5 W
- 3. I = 29.41 A
- 4. X = 9.2 Ω
- 5. C = 159.2 µF
- 6. cos φ = 0.7571