A single-phase load draws 14 A (rms) from a 240 V (rms) supply at a power factor of 0.85 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A load takes 43 kW of real power and 15.5 kvar of reactive power (lagging). Find the apparent power S.
A single-phase motor takes 36 kW at a power factor of 0.75 lagging from a 400 V supply. Find the line current I.
Two loads are connected in parallel to a 240 V single-phase supply: a 9 kW load at a power factor of 0.8 lagging and a 4 kW heater (unity power factor). Find the total current I drawn from the supply.
A single-phase load takes 35 kW at a power factor of 0.65 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
A single-phase load takes 21 kW at a power factor of 0.8 lagging from a 240 V, 50 Hz supply. A 470 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. P = 2856 W
- 2. S = 45.71 kVA
- 3. I = 120 A
- 4. I = 61.03 A
- 5. C = 1695 µF
- 6. I = 92.56 A