A single-phase load connected to a 240 V supply takes 16.5 kW and 16 kvar. Find the current I drawn from the supply.
AC power & power factor worksheet with answers
A single-phase load draws 20 A (rms) from a 240 V (rms) supply at a power factor of 0.85 lagging. Find the real power P it takes.
A single-phase motor takes 19 kW at a power factor of 0.9 lagging from a 400 V supply. Find the line current I.
A load with impedance Z = 6 + j8 Ω is connected to a 240 V (rms) single-phase supply. Find the apparent power S.
A 10 V (rms), 1000 Hz source has an internal impedance Zs = 10 + j10 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A single-phase load takes 9 kW at a power factor of 0.6 lagging from a 230 V, 50 Hz supply. A 100 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
Answer key
- 1. I = 95.77 A
- 2. P = 4080 W
- 3. I = 52.78 A
- 4. S = 5760 VA
- 5. Pmax = 2.5 W
- 6. cos φ = 0.6566