A single-phase load connected to a 120 V supply takes 26 kW and 18 kvar. Find the current I drawn from the supply.
AC power & power factor worksheet with answers
A load takes 37.5 kW of real power and 24.5 kvar of reactive power (lagging). Find the power factor cos φ.
A single-phase motor takes 23 kW at a power factor of 0.85 lagging from a 240 V supply. Find the reactive power Q it draws.
A single-phase motor takes 32 kW at a power factor of 0.65 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase load takes 29 kW at a power factor of 0.7 lagging from a 400 V, 50 Hz supply. A 100 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A single-phase load takes 5 kW at a power factor of 0.6 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the capacitance C needed.
Answer key
- 1. I = 263.5 A
- 2. cos φ = 0.8372
- 3. Q = 14.25 kvar
- 4. Q = 37.41 kvar
- 5. cos φ = 0.7631
- 6. C = 277.6 µF