A single-phase load connected to a 230 V supply takes 24.5 kW and 17.5 kvar. Find the current I drawn from the supply.
AC power & power factor worksheet with answers
A single-phase load draws 11 A (rms) from a 400 V (rms) supply at a power factor of 0.75 lagging. Find the real power P it takes.
A load with impedance Z = 4 + j3 Ω is connected to a 240 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A single-phase motor takes 37 kW at a power factor of 0.7 lagging from a 240 V supply. Find the line current I.
A single-phase load takes 25 kW at a power factor of 0.6 lagging from a 230 V, 60 Hz supply. A 220 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A single-phase load takes 30 kW at a power factor of 0.75 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the capacitance C needed.
Answer key
- 1. I = 130.9 A
- 2. P = 3300 W
- 3. Q = 6912 var
- 4. I = 220.2 A
- 5. cos φ = 0.6536
- 6. C = 629.9 µF