A load takes 34 kW of real power and 34.5 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A single-phase load draws 18 A (rms) from a 120 V (rms) supply at a power factor of 0.65 lagging. Find the reactive power Q it takes.
An inductive load takes 14 A and 2856 W from a 240 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
An inductive load takes 6.5 A and 585 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A single-phase load takes 40 kW at a power factor of 0.8 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
A 150 kVA single-phase transformer supplies a load of 64 kW at a power factor of 0.65 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. cos φ = 0.7019
- 2. Q = 1641 var
- 3. X = 9.031 Ω
- 4. X = 12.21 Ω
- 5. C = 1097 µF
- 6. ΔP = 66.01 kW
Full step-by-step solutions: practise this topic on examproblems.com.