A single-phase load connected to a 120 V supply takes 23 kW and 16.5 kvar. Find the current I drawn from the supply.
AC power & power factor worksheet with answers
A single-phase load draws 8 A (rms) from a 120 V (rms) supply at a power factor of 0.8 lagging. Find the real power P it takes.
A single-phase motor takes 22 kW at a power factor of 0.85 lagging from a 400 V supply. Find the reactive power Q it draws.
An inductive load takes 5.5 A and 1188 W from a 240 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A 120 V (rms), 50 Hz source has an internal impedance Zs = 2 + j3 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A single-phase load takes 5 kW at a power factor of 0.75 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the new line current Inew.
Answer key
- 1. I = 235.9 A
- 2. P = 768 W
- 3. Q = 13.63 kvar
- 4. R = 39.27 Ω
- 5. Pmax = 1800 W
- 6. Inew = 12.76 A