A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 120 V, 14 A and 1008 W. Find the reactive power Q taken by the load.
AC power & power factor worksheet with answers
A single-phase load draws 16 A (rms) from a 230 V (rms) supply at a power factor of 0.75 lagging. Find the real power P it takes.
A single-phase motor takes 28 kW at a power factor of 0.6 lagging from a 240 V supply. Find the reactive power Q it draws.
A single-phase motor takes 32 kW at a power factor of 0.8 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase load takes 16 kW at a power factor of 0.7 lagging from a 400 V, 50 Hz supply. A 33 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A 10 V (rms), 50 Hz source has an internal impedance Zs = 10 + j5 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
Answer key
- 1. Q = 1344 var
- 2. P = 2760 W
- 3. Q = 37.33 kvar
- 4. Q = 24 kvar
- 5. cos φ = 0.7372
- 6. Pmax = 2.5 W
Full step-by-step solutions: practise this topic on examproblems.com.