A single-phase load draws 8 A (rms) from a 400 V (rms) supply at a power factor of 0.9 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load draws 3 A (rms) from a 240 V (rms) supply at a power factor of 0.6 lagging. Find the reactive power Q it takes.
An inductive load takes 13.5 A and 2174 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A load with impedance Z = 3 + j4 Ω is connected to a 230 V (rms) single-phase supply. Find the apparent power S.
A 100 kVA single-phase transformer supplies a load of 51 kW at a power factor of 0.75 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A single-phase load takes 30 kW at a power factor of 0.65 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the capacitance C needed.
Answer key
- 1. P = 2880 W
- 2. Q = 576 var
- 3. R = 11.93 Ω
- 4. S = 10580 VA
- 5. ΔP = 38.31 kW
- 6. C = 408.7 µF