A single-phase load connected to a 400 V supply takes 27.5 kW and 20.5 kvar. Find the current I drawn from the supply.
AC power & power factor worksheet with answers
A single-phase load draws 20 A (rms) from a 240 V (rms) supply at a power factor of 0.9 lagging. Find the real power P it takes.
A single-phase motor takes 21 kW at a power factor of 0.6 lagging from a 240 V supply. Find the line current I.
A single-phase motor takes 18 kW at a power factor of 0.65 lagging from a 230 V supply. Find the line current I.
A single-phase load takes 50 kW at a power factor of 0.75 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the new line current Inew.
A single-phase load takes 30 kW at a power factor of 0.65 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the reactive power QC the capacitor must supply.
Answer key
- 1. I = 85.75 A
- 2. P = 4320 W
- 3. I = 145.8 A
- 4. I = 120.4 A
- 5. Inew = 212.6 A
- 6. QC = 28.98 kvar