A single-phase load draws 2 A (rms) from a 400 V (rms) supply at a power factor of 0.85 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load draws 15 A (rms) from a 240 V (rms) supply at a power factor of 0.85 lagging. Find the real power P it takes.
An inductive load takes 5 A and 978 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A load with impedance Z = 6 + j8 Ω is connected to a 120 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A single-phase load takes 40 kW at a power factor of 0.65 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
A 120 V (rms), 60 Hz source has an internal impedance Zs = 20 + j20 Ω. The load impedance ZL can be chosen freely. The load for maximum power is built from a resistor in series with a capacitor. Find the capacitance C.
Answer key
- 1. P = 680 W
- 2. P = 3060 W
- 3. X = 24.2 Ω
- 4. Q = 1152 var
- 5. Inew = 111.1 A
- 6. C = 132.6 µF