A single-phase load draws 2 A (rms) from a 400 V (rms) supply at a power factor of 0.65 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 6.5 A and 1121 W. Find the power factor cos φ of the load.
A load with impedance Z = 12 + j9 Ω is connected to a 230 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A single-phase motor takes 20 kW at a power factor of 0.6 lagging from a 230 V supply. Find the line current I.
A 100 V (rms), 1000 Hz source has an internal impedance Zs = 4 + j10 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A single-phase load takes 35 kW at a power factor of 0.8 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the capacitance C needed.
Answer key
- 1. P = 520 W
- 2. cos φ = 0.7498
- 3. Q = 2116 var
- 4. I = 144.9 A
- 5. Pmax = 625 W
- 6. C = 244.5 µF