A single-phase load draws 16 A (rms) from a 230 V (rms) supply at a power factor of 0.65 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load draws 12 A (rms) from a 400 V (rms) supply at a power factor of 0.8 lagging. Find the real power P it takes.
Two loads are connected in parallel to a 230 V single-phase supply: a 17 kW load at a power factor of 0.8 lagging and an 8 kW heater (unity power factor). Find the total current I drawn from the supply.
Two loads are connected in parallel to a 230 V single-phase supply: a 9 kW load at a power factor of 0.65 lagging and a 13 kW heater (unity power factor). Find the overall power factor cos φ seen by the supply.
A single-phase load takes 5 kW at a power factor of 0.7 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the reactive power QC the capacitor must supply.
A single-phase load takes 35 kW at a power factor of 0.75 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the capacitance C needed.
Answer key
- 1. Q = 2797 var
- 2. P = 3840 W
- 3. I = 122 A
- 4. cos φ = 0.9021
- 5. QC = 2.679 kvar
- 6. C = 891.7 µF
Full step-by-step solutions: practise this topic on examproblems.com.