A single-phase load draws 13 A (rms) from a 230 V (rms) supply at a power factor of 0.6 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load connected to a 240 V supply takes 28 kW and 21.5 kvar. Find the current I drawn from the supply.
A single-phase motor takes 14 kW at a power factor of 0.75 lagging from a 400 V supply. Find the line current I.
An inductive load takes 9.5 A and 1530 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A 75 kVA single-phase transformer supplies a load of 23 kW at a power factor of 0.65 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A 100 kVA single-phase transformer supplies a load of 53 kW at a power factor of 0.7 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. P = 1794 W
- 2. I = 147.1 A
- 3. I = 46.67 A
- 4. X = 17.28 Ω
- 5. ΔP = 47.01 kW
- 6. ΔP = 31.12 kW