A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 120 V, 15 A and 1440 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A single-phase load connected to a 240 V supply takes 8.5 kW and 11 kvar. Find the current I drawn from the supply.
A single-phase motor takes 37 kW at a power factor of 0.65 lagging from a 400 V supply. Find the reactive power Q it draws.
An inductive load takes 5 A and 300 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A single-phase load takes 25 kW at a power factor of 0.6 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
A 100 V (rms), 50 Hz source has an internal impedance Zs = 5 + j20 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
Answer key
- 1. cos φ = 0.8
- 2. I = 57.92 A
- 3. Q = 43.26 kvar
- 4. R = 12 Ω
- 5. C = 468.5 µF
- 6. Pmax = 500 W
Full step-by-step solutions: practise this topic on examproblems.com.