A single-phase load draws 4 A (rms) from a 400 V (rms) supply at a power factor of 0.75 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load connected to a 120 V supply takes 17.5 kW and 13.5 kvar. Find the current I drawn from the supply.
A single-phase motor takes 14 kW at a power factor of 0.8 lagging from a 400 V supply. Find the reactive power Q it draws.
An inductive load takes 17.5 A and 1785 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A single-phase load takes 14 kW at a power factor of 0.75 lagging from a 240 V, 60 Hz supply. A 68 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A single-phase load takes 10 kW at a power factor of 0.65 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the new line current Inew.
Answer key
- 1. P = 1200 W
- 2. I = 184.2 A
- 3. Q = 10.5 kvar
- 4. R = 5.829 Ω
- 5. cos φ = 0.7899
- 6. Inew = 45.29 A