A single-phase load draws 6 A (rms) from a 230 V (rms) supply at a power factor of 0.8 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load draws 20 A (rms) from a 120 V (rms) supply at a power factor of 0.7 lagging. Find the real power P it takes.
A single-phase motor takes 31 kW at a power factor of 0.7 lagging from a 400 V supply. Find the line current I.
Two loads are connected in parallel to a 240 V single-phase supply: a 24 kW load at a power factor of 0.65 lagging and a 25 kW load at a power factor of 0.8 leading. Find the total current I drawn from the supply.
A single-phase load takes 50 kW at a power factor of 0.65 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the reactive power QC the capacitor must supply.
A single-phase load takes 10 kW at a power factor of 0.8 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the reactive power QC the capacitor must supply.
Answer key
- 1. P = 1104 W
- 2. P = 1680 W
- 3. I = 110.7 A
- 4. I = 207.8 A
- 5. QC = 48.3 kvar
- 6. QC = 5.469 kvar
Full step-by-step solutions: practise this topic on examproblems.com.