A single-phase load connected to a 400 V supply takes 9.5 kW and 3.5 kvar. Find the current I drawn from the supply.
AC power & power factor worksheet with answers
A single-phase load connected to a 400 V supply takes 17 kW and 16.5 kvar. Find the current I drawn from the supply.
An inductive load takes 7 A and 1512 W from a 240 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A single-phase motor takes 39 kW at a power factor of 0.85 lagging from a 230 V supply. Find the line current I.
A single-phase load takes 35 kW at a power factor of 0.8 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the reactive power QC the capacitor must supply.
A 230 V (rms), 1000 Hz source has an internal impedance Zs = 2 + j15 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
Answer key
- 1. I = 25.31 A
- 2. I = 59.23 A
- 3. R = 30.86 Ω
- 4. I = 199.5 A
- 5. QC = 14.75 kvar
- 6. Pmax = 6613 W
Full step-by-step solutions: practise this topic on examproblems.com.