A single-phase load draws 2 A (rms) from a 230 V (rms) supply at a power factor of 0.95 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 5 A and 840 W. Find the power factor cos φ of the load.
Two loads are connected in parallel to a 240 V single-phase supply: a 27 kW load at a power factor of 0.75 lagging and a 23 kW load at a power factor of 0.95 leading. Find the total current I drawn from the supply.
A single-phase motor takes 32 kW at a power factor of 0.7 lagging from a 400 V supply. Find the line current I.
A single-phase load takes 50 kW at a power factor of 0.8 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the new line current Inew.
A 230 V (rms), 1000 Hz source has an internal impedance Zs = 50 + j20 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
Answer key
- 1. P = 437 W
- 2. cos φ = 0.7
- 3. I = 219.1 A
- 4. I = 114.3 A
- 5. Inew = 228.8 A
- 6. Pmax = 264.5 W