A single-phase load draws 11 A (rms) from a 400 V (rms) supply at a power factor of 0.9 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 9 A and 1242 W. Find the reactive power Q taken by the load.
A single-phase motor takes 39 kW at a power factor of 0.75 lagging from a 400 V supply. Find the line current I.
A load with impedance Z = 6 + j8 Ω is connected to a 240 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A single-phase load takes 5 kW at a power factor of 0.6 lagging from a 230 V, 50 Hz supply. A 47 µF capacitor is connected in parallel with the load. Find the new line current I.
A 100 kVA single-phase transformer supplies a load of 53 kW at a power factor of 0.8 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. Q = 1918 var
- 2. Q = 1656 var
- 3. I = 130 A
- 4. Q = 4608 var
- 5. I = 33.58 A
- 6. ΔP = 38.76 kW