A single-phase load draws 10 A (rms) from a 400 V (rms) supply at a power factor of 0.65 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load draws 16 A (rms) from a 400 V (rms) supply at a power factor of 0.6 lagging. Find the reactive power Q it takes.
Two loads are connected in parallel to a 240 V single-phase supply: a 13 kW load at a power factor of 0.65 lagging and a 5 kW load at a power factor of 0.85 lagging. Find the overall power factor cos φ seen by the supply.
A single-phase motor takes 28 kW at a power factor of 0.8 lagging from a 230 V supply. Find the reactive power Q it draws.
A 75 kVA single-phase transformer supplies a load of 30 kW at a power factor of 0.65 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A 100 kVA single-phase transformer supplies a load of 27 kW at a power factor of 0.75 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. Q = 3040 var
- 2. Q = 5120 var
- 3. cos φ = 0.7013
- 4. Q = 21 kvar
- 5. ΔP = 36.29 kW
- 6. ΔP = 70.12 kW
Full step-by-step solutions: practise this topic on examproblems.com.