A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 9.5 A and 1748 W. Find the reactive power Q taken by the load.
AC power & power factor worksheet with answers
A single-phase load draws 12 A (rms) from a 120 V (rms) supply at a power factor of 0.9 lagging. Find the real power P it takes.
A load with impedance Z = 5 + j12 Ω is connected to a 120 V (rms) single-phase supply. Find the real power P it absorbs.
Two loads are connected in parallel to a 240 V single-phase supply: a 28 kW load at a power factor of 0.75 lagging and a 6 kW heater (unity power factor). Find the total current I drawn from the supply.
A 120 V (rms), 1000 Hz source has an internal impedance Zs = 10 + j20 Ω. The load impedance ZL can be chosen freely. The load for maximum power is built from a resistor in series with a capacitor. Find the capacitance C.
A single-phase load takes 10 kW at a power factor of 0.6 lagging from a 240 V, 60 Hz supply. A 100 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. Q = 1311 var
- 2. P = 1296 W
- 3. P = 426 W
- 4. I = 175.1 A
- 5. C = 7.958 µF
- 6. I = 62.44 A
Full step-by-step solutions: practise this topic on examproblems.com.