Hot oil (1.5 kg/s, cp = 2.3 kJ/(kg·K)) cools from 110 to 80 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a parallel-flow heat exchanger the hot fluid cools from 115 to 60 °C while the cold fluid heats from 30 to 40 °C. Find the log-mean temperature difference ΔTlm.
A counter-flow heat exchanger transfers 410 kW. The hot fluid cools from 80 to 55 °C and the cold fluid heats from 15 to 65 °C. The overall heat transfer coefficient is 500 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 90 kW. The hot fluid cools from 155 to 125 °C and the cold fluid heats from 25 to 85 °C. The overall heat transfer coefficient is 1500 W/(m²·K). Find the heat transfer area A needed.
In a parallel-flow double-pipe heat exchanger, hot oil (0.8 kg/s, cp = 2.3 kJ/(kg·K)) flows in the inner tube and cools from 105 to 70 °C. Water (1.5 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 10 °C. The inner tube has a diameter of 25 mm, and U = 250 W/(m²·K) is based on this diameter. Find the tube length L needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 1.5 kW/K. The hot stream enters at 85 °C and the cold stream at 25 °C. The exchanger has A = 4 m² and U = 500 W/(m²·K). Find the hot outlet temperature Th,out.
Answer key
- 1. Tc,out = 33.25 °C
- 2. ΔTlm = 44.92 K
- 3. A = 32.17 m²
- 4. A = 0.7133 m²
- 5. L = 46.9 m
- 6. Th,out = 50.71 °C
Full step-by-step solutions: practise this topic on examproblems.com.