Hot oil (1.5 kg/s, cp = 2.5 kJ/(kg·K)) cools from 130 to 70 °C in a counter-flow exchanger. It heats 1.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 10 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 175 to 75 °C while the cold fluid heats from 20 to 35 °C. Find the log-mean temperature difference ΔTlm.
A counter-flow heat exchanger transfers 410 kW. The hot fluid cools from 115 to 45 °C and the cold fluid heats from 20 to 105 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 40 kW. The hot fluid cools from 135 to 65 °C and the cold fluid heats from 30 to 50 °C. The overall heat transfer coefficient is 800 W/(m²·K). Find the heat transfer area A needed.
Hot oil (2 kg/s, cp = 2.5 kJ/(kg·K)) cools from 175 to 145 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 30 °C. With U = 1000 W/(m²·K), find the heat transfer area A needed.
Hot oil (2 kg/s, cp = 2.1 kJ/(kg·K)) cools from 115 to 85 °C in a counter-flow exchanger. It heats 1.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 10 °C. With U = 800 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Tc,out = 45.89 °C
- 2. ΔTlm = 90.98 K
- 3. A = 83.48 m²
- 4. A = 0.8873 m²
- 5. A = 1.24 m²
- 6. A = 1.972 m²
Full step-by-step solutions: practise this topic on examproblems.com.