Hot oil (0.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 105 to 75 °C in a counter-flow exchanger. It heats 0.8 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 20 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
A counter-flow heat exchanger has a heat transfer area of 2.5 m² and an overall heat transfer coefficient of 500 W/(m²·K). The hot fluid cools from 135 to 35 °C and the cold fluid heats from 15 to 30 °C. Find the heat transfer rate Q̇.
A counter-flow heat exchanger transfers 310 kW. Its heat transfer area is 3 m². The hot fluid cools from 105 to 85 °C and the cold fluid heats from 10 to 80 °C. Find the overall heat transfer coefficient U.
A counter-flow heat exchanger transfers 300 kW. Its heat transfer area is 3 m². The hot fluid cools from 125 to 50 °C and the cold fluid heats from 30 to 50 °C. Find the overall heat transfer coefficient U.
Hot oil (0.5 kg/s, cp = 2.5 kJ/(kg·K)) cools from 115 to 40 °C in a counter-flow exchanger. It heats 0.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. With U = 800 W/(m²·K), find the heat transfer area A needed.
Hot oil (1.5 kg/s, cp = 2.5 kJ/(kg·K)) cools from 85 to 55 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 10 °C. With U = 1000 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Tc,out = 29.42 °C
- 2. Q̇ = 64.07 kW
- 3. U = 2270 W/(m²·K)
- 4. U = 2403 W/(m²·K)
- 5. A = 3.075 m²
- 6. A = 2.129 m²
Full step-by-step solutions: practise this topic on examproblems.com.