Hot oil (2 kg/s, cp = 2.3 kJ/(kg·K)) cools from 160 to 115 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 20 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 160 to 80 °C while the cold fluid heats from 20 to 130 °C. Find the log-mean temperature difference ΔTlm.
A parallel-flow heat exchanger transfers 410 kW. The hot fluid cools from 120 to 40 °C and the cold fluid heats from 20 to 30 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 420 kW. The hot fluid cools from 90 to 50 °C and the cold fluid heats from 10 to 45 °C. The overall heat transfer coefficient is 1500 W/(m²·K). Find the heat transfer area A needed.
Hot oil (2 kg/s, cp = 2.3 kJ/(kg·K)) cools from 140 to 105 °C in a counter-flow exchanger. It heats 0.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 1500 W/(m²·K), find the heat transfer area A needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 0.5 kW/K. The hot stream enters at 160 °C and the cold stream at 15 °C. The exchanger has A = 0.5 m² and U = 500 W/(m²·K). Find the hot outlet temperature Th,out.
Answer key
- 1. Tc,out = 36.51 °C
- 2. ΔTlm = 43.28 K
- 3. A = 34.97 m²
- 4. A = 6.596 m²
- 5. A = 1.903 m²
- 6. Th,out = 111.7 °C
Full step-by-step solutions: practise this topic on examproblems.com.