In a parallel-flow heat exchanger the hot fluid cools from 110 to 95 °C while the cold fluid heats from 25 to 35 °C. Find the log-mean temperature difference ΔTlm.
Heat exchangers (LMTD) worksheet with answers
Hot oil (1 kg/s, cp = 2.3 kJ/(kg·K)) cools from 125 to 85 °C in a counter-flow exchanger. It heats 0.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 20 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
In a condenser, steam condenses at a constant 140 °C on the outside of the tubes. Cooling water (2 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 20 to 90 °C. The overall heat transfer coefficient is 3500 W/(m²·K). Find the heat transfer area A needed.
A parallel-flow heat exchanger transfers 50 kW. The hot fluid cools from 80 to 55 °C and the cold fluid heats from 20 to 30 °C. The overall heat transfer coefficient is 200 W/(m²·K). Find the heat transfer area A needed.
In a parallel-flow double-pipe heat exchanger, hot oil (0.3 kg/s, cp = 2.5 kJ/(kg·K)) flows in the inner tube and cools from 95 to 65 °C. Water (1.5 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 25 °C. The inner tube has a diameter of 25 mm, and U = 150 W/(m²·K) is based on this diameter. Find the tube length L needed.
Hot oil (0.5 kg/s, cp = 2.5 kJ/(kg·K)) cools from 175 to 110 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 500 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. ΔTlm = 71.78 K
- 2. Tc,out = 64.02 °C
- 3. A = 2.091 m²
- 4. A = 6.253 m²
- 5. L = 37.16 m
- 6. A = 1.531 m²