A counter-flow heat exchanger has a heat transfer area of 20 m² and an overall heat transfer coefficient of 1000 W/(m²·K). The hot fluid cools from 95 to 65 °C and the cold fluid heats from 10 to 75 °C. Find the heat transfer rate Q̇.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 150 to 120 °C while the cold fluid heats from 20 to 130 °C. Find the log-mean temperature difference ΔTlm.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 170 kW. The hot fluid cools from 90 to 75 °C and the cold fluid heats from 30 to 70 °C. The LMTD correction factor for this arrangement is F = 0.95, and U = 1000 W/(m²·K). Find the heat transfer area A needed.
A parallel-flow heat exchanger transfers 340 kW. Its heat transfer area is 2 m². The hot fluid cools from 150 to 100 °C and the cold fluid heats from 15 to 40 °C. Find the overall heat transfer coefficient U.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 2 kW/K. The hot stream enters at 130 °C and the cold stream at 10 °C. The exchanger has A = 5 m² and U = 300 W/(m²·K). Find the hot outlet temperature Th,out.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 1 kW/K. The hot stream enters at 145 °C and the cold stream at 15 °C. The exchanger has A = 1.5 m² and U = 800 W/(m²·K). Find the hot outlet temperature Th,out.
Answer key
- 1. Q̇ = 692 kW
- 2. ΔTlm = 49.71 K
- 3. A = 5.805 m²
- 4. U = 1838 W/(m²·K)
- 5. Th,out = 78.57 °C
- 6. Th,out = 74.09 °C