In a parallel-flow heat exchanger the hot fluid cools from 140 to 115 °C while the cold fluid heats from 25 to 50 °C. Find the log-mean temperature difference ΔTlm.
Heat exchangers (LMTD) worksheet with answers
Hot oil (2 kg/s, cp = 2.3 kJ/(kg·K)) cools from 100 to 55 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 30 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
A counter-flow heat exchanger transfers 420 kW. The hot fluid cools from 165 to 135 °C and the cold fluid heats from 10 to 90 °C. The overall heat transfer coefficient is 1000 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 150 kW. The hot fluid cools from 150 to 120 °C and the cold fluid heats from 25 to 75 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.
Hot oil (2 kg/s, cp = 2.5 kJ/(kg·K)) cools from 100 to 55 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 800 W/(m²·K), find the heat transfer area A needed.
Hot oil (0.5 kg/s, cp = 2.3 kJ/(kg·K)) cools from 170 to 150 °C in a counter-flow exchanger. It heats 0.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 20 °C. With U = 300 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. ΔTlm = 87.64 K
- 2. Tc,out = 46.51 °C
- 3. A = 4.291 m²
- 4. A = 5.91 m²
- 5. A = 7.337 m²
- 6. A = 0.5702 m²
Full step-by-step solutions: practise this topic on examproblems.com.