A balanced Δ-connected load has an impedance of 9 + j12 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 480 V. Find the magnitude of the phase current Iph flowing through each impedance.
Three-phase power worksheet with answers
A balanced Δ-connected load has an impedance of 3 + j4 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 400 V. Find the magnitude of the phase current Iph flowing through each impedance.
A balanced three-phase load draws a line current of 25 A from a supply with a line-to-line voltage of 690 V. The power factor is 0.8 lagging. Find the total real power P drawn by the load in kW.
A balanced three-phase load draws a line current of 10 A from a supply with a line-to-line voltage of 480 V. The power factor is 0.95 lagging. Find the total real power P drawn by the load in kW.
A balanced three-phase load takes 60 kW at a power factor of 0.78 lagging from a 690 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
A balanced three-phase load takes 80 kW at a power factor of 0.8 lagging from a 400 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.98 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
Answer key
- 1. Iph = 32 A
- 2. Iph = 80 A
- 3. P = 23.9 kW
- 4. P = 7.898 kW
- 5. Cph = 52.77 µF
- 6. Cph = 290.2 µF
Full step-by-step solutions: practise this topic on examproblems.com.