A balanced Y-connected load has an impedance of 18 + j24 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 400 V. Find the magnitude of the line current IL.
Three-phase power worksheet with answers
A balanced Δ-connected load has an impedance of 6 + j8 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 400 V. Find the magnitude of the phase current Iph flowing through each impedance.
A balanced Δ-connected load with an impedance of 12 + j9 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 208 V. Find the total real power P absorbed by the load in kW.
A balanced Δ-connected load with an impedance of 16 + j12 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 400 V. Find the total real power P absorbed by the load in kW.
A balanced three-phase load takes 100 kW at a power factor of 0.7 lagging from a 690 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.98 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.
A balanced three-phase load takes 60 kW at a power factor of 0.65 lagging from a 415 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.
Answer key
- 1. IL = 7.698 A
- 2. Iph = 40 A
- 3. P = 6.922 kW
- 4. P = 19.2 kW
- 5. Cph = 546.3 µF
- 6. Cph = 759.4 µF
Full step-by-step solutions: practise this topic on examproblems.com.