An ideal transformer must step 8000 V down to 400 V. Its primary winding has 500 turns. How many turns N2 does the secondary winding need?
Transformers worksheet with answers
An ideal transformer must step 6000 V down to 120 V. Its primary winding has 7500 turns. How many turns N2 does the secondary winding need?
An ideal transformer with a turns ratio N₁:N₂ = 10:1 has 2400 V applied to its primary winding. A 12 Ω resistor is connected across the secondary winding. Find the primary current I1.
A single-phase 500 kVA, 6600/230 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.
A single-phase 75 kVA transformer has a core loss of 600 W and a copper loss of 2400 W at rated load. It supplies 50% of its rated kVA at a power factor of 0.85 lagging. Find the total losses Ploss in watts at this load.
A single-phase 150 kVA transformer has a core loss of 450 W and a copper loss of 1350 W at rated load. It supplies 25% of its rated kVA at a power factor of 0.95 lagging. Find the total losses Ploss in watts at this load.
Answer key
- 1. N2 = 25
- 2. N2 = 150
- 3. I1 = 2 A
- 4. IHV = 75.76 A
- 5. Ploss = 1200 W
- 6. Ploss = 534.4 W
Full step-by-step solutions: practise this topic on examproblems.com.