An ideal transformer must step 10000 V down to 400 V. Its primary winding has 625 turns. How many turns N2 does the secondary winding need?
Transformers worksheet with answers
An ideal transformer has 250 turns on its primary winding and 2000 turns on its secondary winding. The primary is connected to a 120 V AC supply. Find the secondary voltage V2.
A single-phase 75 kVA, 7200/240 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.
A 10 Ω resistor is connected across the secondary winding of an ideal transformer with a turns ratio N₁:N₂ = 8:1. Find the resistance R1′ seen looking into the primary winding.
A single-phase 75 kVA transformer has a core loss of 375 W and a copper loss of 937.5 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
A single-phase 200 kVA transformer has a core loss of 1000 W and a copper loss of 2500 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
Answer key
- 1. N2 = 25
- 2. V2 = 960 V
- 3. ILV = 312.5 A
- 4. R1′ = 640 Ω
- 5. Sη,max = 47.43 kVA
- 6. Sη,max = 126.5 kVA