1 公式与方法热传导
傅里叶定律 Q̇ = kAΔT/L
导热热阻 R = L/(kA)
对流热阻 R = 1/(hA)
串联热阻 Q̇ = ΔTtotal /ΣR
U 值 U = 1/(ΣR·A)
换热器 (LMTD)
热负荷 Q = U·A·ΔTlm
对数平均温差 ΔTlm = (ΔT1 − ΔT2 )/ln(ΔT1 /ΔT2 )
物流热量衡算 Q = ṁcp (Tin − Tout )
2 练习题1. 热传导 中等
玻璃, k = 0.96 100 mm 木材, k = 0.17 25 mm 25 °C 5 °C Ti = ? Q̇ 一面墙由 100 mm 的玻璃和 25 mm 的木材组成,面积为 15 m²。外表面温度为 25 °C 和 5 °C。 求两层交界面处的温度 Ti 。
L1 = 100 mm, k1 = 0.96 W/(m·K) L2 = 25 mm, k2 = 0.17 W/(m·K) A = 15 m² T1 = 25 °C T3 = 5 °C
Ti = °C
2. 热传导 困难
玻璃, k = 0.96 250 mm 矿棉, k = 0.04 150 mm 室内 22 °C 室外 -14 °C Q̇ 由 250 mm 玻璃和 150 mm 矿棉组成的墙,将 22 °C 的房间与 -14 °C 的室外空气隔开。对流换热系数室内为 7.7 W/(m²·K),室外为 30 W/(m²·K),墙面积为 20 m²。 求墙体的总传热系数 U 。
L1 = 250 mm, k1 = 0.96 W/(m·K) L2 = 150 mm, k2 = 0.04 W/(m·K) A = 20 m² hi = 7.7 W/(m²·K) ho = 30 W/(m²·K) Troom = 22 °C Tout = -14 °C
U = W/(m²·K)
3. 换热器 (LMTD) 中等
长度 T 120 °C 20 °C 105 °C ΔT₁ ΔT₂ 冷凝蒸汽 在冷凝器中,蒸汽在管外以恒定的 120 °C 冷凝。冷却水(2 kg/s,cp = 4.18 kJ/(kg·K))在管内流动,从 20 °C 加热到 105 °C。总传热系数为 2000 W/(m²·K)。求所需的传热面积 A 。
Ts = 120 °C ṁ = 2 kg/s cp = 4.18 kJ/(kg·K) Tc : 20 → 105 °C U = 2000 W/(m²·K)
A = m²
4. 换热器 (LMTD) 困难
长度 T 95 °C 50 °C 33.97 °C 25 °C ΔT₁ ΔT₂ 逆流 热油(0.5 kg/s,cp = 2.5 kJ/(kg·K))在逆流换热器中从 95 冷却到 50 °C。它加热 1.5 kg/s 的水(cp = 4.18 kJ/(kg·K)),水的入口温度为 25 °C。已知 U = 500 W/(m²·K),求所需传热面积 A 。
ṁh = 0.5 kg/s cp,h = 2.5 kJ/(kg·K) Th : 95 → 50 °C ṁc = 1.5 kg/s cp,c = 4.18 kJ/(kg·K) Tc,in = 25 °C U = 500 W/(m²·K)
A = m²
3 溶液1. 热传导
答案: Ti = 16.71 °C
热阻: 通过串联各层的稳态热流类似于通过串联电阻的电流:Q̇ = ΔT/ΣR,导热层 R = L/(kA),对流表面 R = 1/(hA)。各层的温降与其热阻成正比。
各层热阻 R1 = L1 /(k1 A) = (100/1000)/(0.96·15) = 0.006944 K/W
R2 = L2 /(k2 A) = (25/1000)/(0.17·15) = 0.009804 K/W
热流量 Q̇ = (T1 − T3 )/(R1 + R2 ) = 20/0.01675 = 1194 W
交界面温度 第一层中温度下降 Q̇·R₁。
Ti = T1 − Q̇·R1 = 25 − 1194·0.006944 = 16.71 °C
2. 热传导
答案: U = 0.2396 W/(m²·K)
热阻: 通过串联各层的稳态热流类似于通过串联电阻的电流:Q̇ = ΔT/ΣR,导热层 R = L/(kA),对流表面 R = 1/(hA)。各层的温降与其热阻成正比。
串联热阻 Ri = 1/(hi A) = 1/(7.7·20) = 0.006494 K/W
R1 = L1 /(k1 A) = (250/1000)/(0.96·20) = 0.01302 K/W
R2 = L2 /(k2 A) = (150/1000)/(0.04·20) = 0.1875 K/W
Ro = 1/(ho A) = 1/(30·20) = 0.001667 K/W
ΣR = 0.2087 K/W
总传热系数 U = 1/(A·ΣR) = 1/(20·0.2087) = 0.2396 W/(m²·K)
3. 换热器 (LMTD)
答案: A = 7.93 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm , with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
由水侧求热负荷 Q̇ = 2·4.18·(105 − 20) = 710.6 kW
两端温差 ΔT₁ = 120 − 20 = 100 K
ΔT₂ = 120 − 105 = 15 K
对数平均温差 ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (100 − 15)/ln(100/15) = 44.8 K
面积 A = Q̇/(U·ΔTlm ) = 710600/(2000·44.8) = 7.93 m²
4. 换热器 (LMTD)
答案: A = 2.787 m²
对数平均温差法 (LMTD): 两股流体之间的温差沿换热器变化,因此传热方程使用其对数平均值:Q̇ = U·A·ΔTlm ,其中 ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂),ΔT₁ 和 ΔT₂ 为两端温差。进出口温度相同时,逆流的 ΔTlm 大于并流。
热负荷和水的出口温度 Q̇ = ṁh cp,h (Th,in − Th,out ) = 0.5·2.5·45 = 56.25 kW
Tc,out = 25 + 56.25/(1.5·4.18) = 33.97 °C
两端温差 逆流时,热流体入口对着冷流体出口,热流体出口对着冷流体入口。
ΔT₁ = Th,in − Tc,out = 95 − 33.97 = 61.03 K
ΔT₂ = Th,out − Tc,in = 50 − 25 = 25 K
对数平均温差 ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (61.03 − 25)/ln(61.03/25) = 40.37 K
面积 A = Q̇/(U·ΔTlm ) = 56250/(500·40.37) = 2.787 m²