1 公式与方法热传导
傅里叶定律 Q̇ = kAΔT/L
导热热阻 R = L/(kA)
对流热阻 R = 1/(hA)
串联热阻 Q̇ = ΔTtotal /ΣR
U 值 U = 1/(ΣR·A)
换热器 (LMTD)
热负荷 Q = U·A·ΔTlm
对数平均温差 ΔTlm = (ΔT1 − ΔT2 )/ln(ΔT1 /ΔT2 )
物流热量衡算 Q = ṁcp (Tin − Tout )
2 练习题1. 热传导 中等
混凝土, k = 1.4 200 mm 木材, k = 0.17 25 mm 25 °C 4 °C Q̇ = ? 一面墙由 200 mm 的混凝土和 25 mm 的木材组成,面积为 6 m²。外表面温度为 25 °C 和 4 °C。 求通过墙体的热流量 Q̇ 。
L1 = 200 mm, k1 = 1.4 W/(m·K) L2 = 25 mm, k2 = 0.17 W/(m·K) A = 6 m² T1 = 25 °C T3 = 4 °C
Q̇ = W
2. 热传导 困难
木材, k = 0.17 150 mm 发泡聚苯乙烯, k = 0.035 25 mm 室内 21 °C 室外 1 °C Q̇ = ? 由 150 mm 木材和 25 mm 发泡聚苯乙烯组成的墙,将 21 °C 的房间与 1 °C 的室外空气隔开。对流换热系数室内为 8 W/(m²·K),室外为 25 W/(m²·K),墙面积为 12 m²。 求通过墙体的热损失 Q̇ 。
L1 = 150 mm, k1 = 0.17 W/(m·K) L2 = 25 mm, k2 = 0.035 W/(m·K) A = 12 m² hi = 8 W/(m²·K) ho = 25 W/(m²·K) Troom = 21 °C Tout = 1 °C
Q̇ = W
3. 换热器 (LMTD) 中等
长度 T 165 °C 70 °C 30 °C 10 °C ΔT₁ ΔT₂ 逆流 一台管壳式换热器(单壳程、双管程)须传递 230 kW。热流体从 165 °C 冷却到 70 °C,冷流体从 10 °C 加热到 30 °C。该布置的 LMTD 修正系数为 F = 0.92,U = 500 W/(m²·K)。求所需的传热面积 A 。
Q̇ = 230 kW F = 0.92 U = 500 W/(m²·K) Th : 165 → 70 °C Tc : 10 → 30 °C
A = m²
4. 换热器 (LMTD) 困难
长度 T 125 °C 70 °C 25.13 °C 10 °C ΔT₁ ΔT₂ 逆流 热油(1 kg/s,cp = 2.3 kJ/(kg·K))在逆流换热器中从 125 冷却到 70 °C。它加热 2 kg/s 的水(cp = 4.18 kJ/(kg·K)),水的入口温度为 10 °C。已知 U = 500 W/(m²·K),求所需传热面积 A 。
ṁh = 1 kg/s cp,h = 2.3 kJ/(kg·K) Th : 125 → 70 °C ṁc = 2 kg/s cp,c = 4.18 kJ/(kg·K) Tc,in = 10 °C U = 500 W/(m²·K)
A = m²
3 溶液1. 热传导
答案: Q̇ = 434.6 W
热阻: 通过串联各层的稳态热流类似于通过串联电阻的电流:Q̇ = ΔT/ΣR,导热层 R = L/(kA),对流表面 R = 1/(hA)。各层的温降与其热阻成正比。
各层热阻 R1 = L1 /(k1 A) = (200/1000)/(1.4·6) = 0.02381 K/W
R2 = L2 /(k2 A) = (25/1000)/(0.17·6) = 0.02451 K/W
热流量 Q̇ = (T1 − T3 )/(R1 + R2 ) = 21/0.04832 = 434.6 W
2. 热传导
答案: Q̇ = 136.2 W
热阻: 通过串联各层的稳态热流类似于通过串联电阻的电流:Q̇ = ΔT/ΣR,导热层 R = L/(kA),对流表面 R = 1/(hA)。各层的温降与其热阻成正比。
串联热阻 Ri = 1/(hi A) = 1/(8·12) = 0.01042 K/W
R1 = L1 /(k1 A) = (150/1000)/(0.17·12) = 0.07353 K/W
R2 = L2 /(k2 A) = (25/1000)/(0.035·12) = 0.05952 K/W
Ro = 1/(ho A) = 1/(25·12) = 0.003333 K/W
ΣR = 0.1468 K/W
热损失 Q̇ = (21 − (1))/0.1468 = 136.2 W
3. 换热器 (LMTD)
答案: A = 5.406 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm , with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
两端温差(逆流) 逆流时,热流体入口对着冷流体出口,热流体出口对着冷流体入口。
ΔT₁ = Th,in − Tc,out = 165 − 30 = 135 K
ΔT₂ = Th,out − Tc,in = 70 − 10 = 60 K
对数平均温差 ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (135 − 60)/ln(135/60) = 92.49 K
面积 A = Q̇/(U·F·ΔTlm,cf ) = 230000/(500·0.92·92.49) = 5.406 m²
4. 换热器 (LMTD)
答案: A = 3.233 m²
对数平均温差法 (LMTD): 两股流体之间的温差沿换热器变化,因此传热方程使用其对数平均值:Q̇ = U·A·ΔTlm ,其中 ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂),ΔT₁ 和 ΔT₂ 为两端温差。进出口温度相同时,逆流的 ΔTlm 大于并流。
热负荷和水的出口温度 Q̇ = ṁh cp,h (Th,in − Th,out ) = 1·2.3·55 = 126.5 kW
Tc,out = 10 + 126.5/(2·4.18) = 25.13 °C
两端温差 逆流时,热流体入口对着冷流体出口,热流体出口对着冷流体入口。
ΔT₁ = Th,in − Tc,out = 125 − 25.13 = 99.87 K
ΔT₂ = Th,out − Tc,in = 70 − 10 = 60 K
对数平均温差 ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (99.87 − 60)/ln(99.87/60) = 78.25 K
面积 A = Q̇/(U·ΔTlm ) = 126500/(500·78.25) = 3.233 m²