1 公式与方法热传导
傅里叶定律 Q̇ = kAΔT/L
导热热阻 R = L/(kA)
对流热阻 R = 1/(hA)
串联热阻 Q̇ = ΔTtotal /ΣR
U 值 U = 1/(ΣR·A)
换热器 (LMTD)
热负荷 Q = U·A·ΔTlm
对数平均温差 ΔTlm = (ΔT1 − ΔT2 )/ln(ΔT1 /ΔT2 )
物流热量衡算 Q = ṁcp (Tin − Tout )
2 练习题1. 热传导 中等
发泡聚苯乙烯, k = 0.035 250 mm 木材, k = 0.17 100 mm 21 °C -6 °C Q̇ = ? 一面墙由 250 mm 的发泡聚苯乙烯和 100 mm 的木材组成,面积为 10 m²。外表面温度为 21 °C 和 -6 °C。 求通过墙体的热流量 Q̇ 。
L1 = 250 mm, k1 = 0.035 W/(m·K) L2 = 100 mm, k2 = 0.17 W/(m·K) A = 10 m² T1 = 21 °C T3 = -6 °C
Q̇ = W
2. 热传导 困难
混凝土, k = 1.4 200 mm 矿棉, k = 0.04 150 mm 室内 21 °C 室外 -12 °C Q̇ 由 200 mm 混凝土和 150 mm 矿棉组成的墙,将 21 °C 的房间与 -12 °C 的室外空气隔开。对流换热系数室内为 8 W/(m²·K),室外为 30 W/(m²·K),墙面积为 8 m²。 求墙体的总传热系数 U 。
L1 = 200 mm, k1 = 1.4 W/(m·K) L2 = 150 mm, k2 = 0.04 W/(m·K) A = 8 m² hi = 8 W/(m²·K) ho = 30 W/(m²·K) Troom = 21 °C Tout = -12 °C
U = W/(m²·K)
3. 换热器 (LMTD) 中等
长度 T 105 °C 30 °C 70 °C ΔT₁ ΔT₂ 冷凝蒸汽 在冷凝器中,蒸汽在管外以恒定的 105 °C 冷凝。冷却水(5 kg/s,cp = 4.18 kJ/(kg·K))在管内流动,从 30 °C 加热到 70 °C。总传热系数为 3000 W/(m²·K)。求所需的传热面积 A 。
Ts = 105 °C ṁ = 5 kg/s cp = 4.18 kJ/(kg·K) Tc : 30 → 70 °C U = 3000 W/(m²·K)
A = m²
4. 换热器 (LMTD) 困难
长度 T 145 °C 95 °C 85.02 °C 30 °C ΔT₁ ΔT₂ 逆流 热油(2 kg/s,cp = 2.3 kJ/(kg·K))在逆流换热器中从 145 冷却到 95 °C。它加热 1 kg/s 的水(cp = 4.18 kJ/(kg·K)),水的入口温度为 30 °C。已知 U = 800 W/(m²·K),求所需传热面积 A 。
ṁh = 2 kg/s cp,h = 2.3 kJ/(kg·K) Th : 145 → 95 °C ṁc = 1 kg/s cp,c = 4.18 kJ/(kg·K) Tc,in = 30 °C U = 800 W/(m²·K)
A = m²
3 溶液1. 热传导
答案: Q̇ = 34.92 W
热阻: 通过串联各层的稳态热流类似于通过串联电阻的电流:Q̇ = ΔT/ΣR,导热层 R = L/(kA),对流表面 R = 1/(hA)。各层的温降与其热阻成正比。
各层热阻 R1 = L1 /(k1 A) = (250/1000)/(0.035·10) = 0.7143 K/W
R2 = L2 /(k2 A) = (100/1000)/(0.17·10) = 0.05882 K/W
热流量 Q̇ = (T1 − T3 )/(R1 + R2 ) = 27/0.7731 = 34.92 W
2. 热传导
答案: U = 0.2468 W/(m²·K)
热阻: 通过串联各层的稳态热流类似于通过串联电阻的电流:Q̇ = ΔT/ΣR,导热层 R = L/(kA),对流表面 R = 1/(hA)。各层的温降与其热阻成正比。
串联热阻 Ri = 1/(hi A) = 1/(8·8) = 0.01563 K/W
R1 = L1 /(k1 A) = (200/1000)/(1.4·8) = 0.01786 K/W
R2 = L2 /(k2 A) = (150/1000)/(0.04·8) = 0.4688 K/W
Ro = 1/(ho A) = 1/(30·8) = 0.004167 K/W
ΣR = 0.5064 K/W
总传热系数 U = 1/(A·ΣR) = 1/(8·0.5064) = 0.2468 W/(m²·K)
3. 换热器 (LMTD)
答案: A = 5.31 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm , with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
由水侧求热负荷 Q̇ = 5·4.18·(70 − 30) = 836 kW
两端温差 ΔT₁ = 105 − 30 = 75 K
ΔT₂ = 105 − 70 = 35 K
对数平均温差 ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (75 − 35)/ln(75/35) = 52.48 K
面积 A = Q̇/(U·ΔTlm ) = 836000/(3000·52.48) = 5.31 m²
4. 换热器 (LMTD)
答案: A = 4.603 m²
对数平均温差法 (LMTD): 两股流体之间的温差沿换热器变化,因此传热方程使用其对数平均值:Q̇ = U·A·ΔTlm ,其中 ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂),ΔT₁ 和 ΔT₂ 为两端温差。进出口温度相同时,逆流的 ΔTlm 大于并流。
热负荷和水的出口温度 Q̇ = ṁh cp,h (Th,in − Th,out ) = 2·2.3·50 = 230 kW
Tc,out = 30 + 230/(1·4.18) = 85.02 °C
两端温差 逆流时,热流体入口对着冷流体出口,热流体出口对着冷流体入口。
ΔT₁ = Th,in − Tc,out = 145 − 85.02 = 59.98 K
ΔT₂ = Th,out − Tc,in = 95 − 30 = 65 K
对数平均温差 ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (59.98 − 65)/ln(59.98/65) = 62.45 K
面积 A = Q̇/(U·ΔTlm ) = 230000/(800·62.45) = 4.603 m²