1 公式与方法热传导
傅里叶定律 Q̇ = kAΔT/L
导热热阻 R = L/(kA)
对流热阻 R = 1/(hA)
串联热阻 Q̇ = ΔTtotal /ΣR
U 值 U = 1/(ΣR·A)
换热器 (LMTD)
热负荷 Q = U·A·ΔTlm
对数平均温差 ΔTlm = (ΔT1 − ΔT2 )/ln(ΔT1 /ΔT2 )
物流热量衡算 Q = ṁcp (Tin − Tout )
2 练习题1. 热传导 中等
木材, k = 0.17 250 mm 玻璃, k = 0.96 25 mm 15 °C 6 °C Q̇ = ? 一面墙由 250 mm 的木材和 25 mm 的玻璃组成,面积为 8 m²。外表面温度为 15 °C 和 6 °C。 求通过墙体的热流量 Q̇ 。
L1 = 250 mm, k1 = 0.17 W/(m·K) L2 = 25 mm, k2 = 0.96 W/(m·K) A = 8 m² T1 = 15 °C T3 = 6 °C
Q̇ = W
2. 热传导 困难
混凝土, k = 1.4 150 mm 矿棉, k = 0.04 150 mm 室内 22 °C 室外 -14 °C Ts = ? Q̇ 由 150 mm 混凝土和 150 mm 矿棉组成的墙,将 22 °C 的房间与 -14 °C 的室外空气隔开。对流换热系数室内为 6 W/(m²·K),室外为 25 W/(m²·K),墙面积为 8 m²。 求墙内表面的温度 Ts 。
L1 = 150 mm, k1 = 1.4 W/(m·K) L2 = 150 mm, k2 = 0.04 W/(m·K) A = 8 m² hi = 6 W/(m²·K) ho = 25 W/(m²·K) Troom = 22 °C Tout = -14 °C
Ts = °C
3. 换热器 (LMTD) 中等
长度 T 90 °C 60 °C 40 °C 30 °C ΔT₁ ΔT₂ 逆流 一台管壳式换热器(单壳程、双管程)须传递 550 kW。热流体从 90 °C 冷却到 60 °C,冷流体从 30 °C 加热到 40 °C。该布置的 LMTD 修正系数为 F = 0.88,U = 200 W/(m²·K)。求所需的传热面积 A 。
Q̇ = 550 kW F = 0.88 U = 200 W/(m²·K) Th : 90 → 60 °C Tc : 30 → 40 °C
A = m²
4. 换热器 (LMTD) 困难
长度 T 120 °C 45 °C 66.27 °C 25 °C ΔT₁ ΔT₂ 逆流 热油(0.5 kg/s,cp = 2.3 kJ/(kg·K))在逆流换热器中从 120 冷却到 45 °C。它加热 0.5 kg/s 的水(cp = 4.18 kJ/(kg·K)),水的入口温度为 25 °C。已知 U = 500 W/(m²·K),求所需传热面积 A 。
ṁh = 0.5 kg/s cp,h = 2.3 kJ/(kg·K) Th : 120 → 45 °C ṁc = 0.5 kg/s cp,c = 4.18 kJ/(kg·K) Tc,in = 25 °C U = 500 W/(m²·K)
A = m²
3 溶液1. 热传导
答案: Q̇ = 48.11 W
热阻: 通过串联各层的稳态热流类似于通过串联电阻的电流:Q̇ = ΔT/ΣR,导热层 R = L/(kA),对流表面 R = 1/(hA)。各层的温降与其热阻成正比。
各层热阻 R1 = L1 /(k1 A) = (250/1000)/(0.17·8) = 0.1838 K/W
R2 = L2 /(k2 A) = (25/1000)/(0.96·8) = 0.003255 K/W
热流量 Q̇ = (T1 − T3 )/(R1 + R2 ) = 9/0.1871 = 48.11 W
2. 热传导
答案: Ts = 20.52 °C
热阻: 通过串联各层的稳态热流类似于通过串联电阻的电流:Q̇ = ΔT/ΣR,导热层 R = L/(kA),对流表面 R = 1/(hA)。各层的温降与其热阻成正比。
串联热阻 Ri = 1/(hi A) = 1/(6·8) = 0.02083 K/W
R1 = L1 /(k1 A) = (150/1000)/(1.4·8) = 0.01339 K/W
R2 = L2 /(k2 A) = (150/1000)/(0.04·8) = 0.4688 K/W
Ro = 1/(ho A) = 1/(25·8) = 0.005 K/W
ΣR = 0.508 K/W
热损失 Q̇ = (22 − (-14))/0.508 = 70.87 W
Ts = Troom − Q̇·Ri = 22 − 70.87·0.02083 = 20.52 °C
3. 换热器 (LMTD)
答案: A = 79.82 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm , with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
两端温差(逆流) 逆流时,热流体入口对着冷流体出口,热流体出口对着冷流体入口。
ΔT₁ = Th,in − Tc,out = 90 − 40 = 50 K
ΔT₂ = Th,out − Tc,in = 60 − 30 = 30 K
对数平均温差 ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (50 − 30)/ln(50/30) = 39.15 K
面积 A = Q̇/(U·F·ΔTlm,cf ) = 550000/(200·0.88·39.15) = 79.82 m²
4. 换热器 (LMTD)
答案: A = 5.054 m²
对数平均温差法 (LMTD): 两股流体之间的温差沿换热器变化,因此传热方程使用其对数平均值:Q̇ = U·A·ΔTlm ,其中 ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂),ΔT₁ 和 ΔT₂ 为两端温差。进出口温度相同时,逆流的 ΔTlm 大于并流。
热负荷和水的出口温度 Q̇ = ṁh cp,h (Th,in − Th,out ) = 0.5·2.3·75 = 86.25 kW
Tc,out = 25 + 86.25/(0.5·4.18) = 66.27 °C
两端温差 逆流时,热流体入口对着冷流体出口,热流体出口对着冷流体入口。
ΔT₁ = Th,in − Tc,out = 120 − 66.27 = 53.73 K
ΔT₂ = Th,out − Tc,in = 45 − 25 = 20 K
对数平均温差 ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (53.73 − 20)/ln(53.73/20) = 34.13 K
面积 A = Q̇/(U·ΔTlm ) = 86250/(500·34.13) = 5.054 m²